Type Easy

Quick and easy handling

Control components for VAV terminal units, to be mounted on the terminal unit for easy operation

  • Simplified ordering and on-site assignment to rooms as selection is based on the nominal size of the duct
  • Rapid volume flow rate setting without additional device
  • Indicator light simplifies functional checking
  • Proven technology of the Compact volume flow controllers
  • Suitable for constant and variable volume flows as well as for Vmin / Vmax switching

Easyregler LMV-D3A 00135177_0
  • Application
  • Description

Application

  • Electronic volume flow controllers of Type Easy are compact, all-in-one control devices for VAV terminal units
  • Dynamic differential pressure transducer, electronic controller, and actuator are fitted together in one casing
  • Suitable for different control tasks depending on how the input for the setpoint value signal is used
  • The output signals of the room temperature controller, central BMS, air quality controller or similar units control the volume flow rate setpoint
  • Override control by means of switches or relays
  • Volume flow rate actual value is available as linear voltage signal

Standard filtration in comfort air conditioning systems allows for use of the controller in the supply air without additional dust protection. Since a partial volume flow is passed through the transducer in order to measure the volume flow rate, please note:

  • With heavy dust levels in the room, suitable extract air filters must be provided.
  • If the air is polluted with fluff or sticky particles, or if it contains aggressive media, Easy controllers cannot be used

Ausführungen

  • LMV-D3AL-F für LVC
  • 227V-024T-05-013 für LVC
  • LMV-D3A-F für TVR
  • 227V-024T-05-002 für TVR
  • 227V-024T-15-002 für TVJ, TVT
  • SMV-D3A für TVT
  • LMV-D3A für TZ-Silenzio, TA-Silenzio, TVZ, TVA

Operating modes

Variable volume flow

  • Vmin: minimum volume flow rate
  • Vmax: maximum volume flow rate


Constant value

  • Vmin: constant volume flow rate
  • Vmax: 100 %

Signal voltage range

  • 0 – 10 V DC

Bauteile und Eigenschaften

  • Sensor nach dynamischem Messprinzip
  • Mechanische Anschläge zur Begrenzung der Klappenstellungen
  • Überlastsichere Antriebe
  • Entriegelungstaste zur Handbetätigung

Technical information

Function, Technical data, Order code, Produktbeziehungen

  • Function
  • Technical data
Principle of operation – Easy and Compact controllers 00132245_0

① Differential pressure transducer

② Actuator

③ Volume flow controller

④ Setpoint value signal

Funktionsbeschreibung

Charakteristisch für Volumenstrom-Regelgeräte ist ein geschlossener Regelkreis zur Regelung des Volumenstromes, das heißt Messen – Vergleichen – Stellen.

Die Messung des Volumenstromes erfolgt durch Messung eines Differenzdruckes (Wirkdruck). Das Volumenstrom-Regelgerät enthält dazu einen Differenzdrucksensor.

Der Wirkdruck wird vom integrierten Differenzdrucktransmitter in ein Spannungssignal umgesetzt. Der Volumenstrom-Istwert steht als Spannungssignal zur Verfügung. Durch die werkseitige Justage entspricht 10 V DC immer dem Nennvolumenstrom (VNenn).

Der Volumenstrom-Sollwert wird von einem übergeordneten Regler (z. B. Raumtemperaturregler, Luftqualitätsregler, Gebäudeleittechnik) oder durch Schaltkontakte vorgegeben. Die variable Volumenstromregelung erfolgt zwischen Vmin und Vmax. Die Übersteuerung der Raumtemperaturregelung durch Zwangsschaltungen, beispielsweise Absperrung, ist möglich.

Der Regler vergleicht den Volumenstrom-Sollwert mit dem aktuellen Istwert und steuert der Regelabweichung entsprechend den internen Stellantrieb.

Volumenstrom-Parameter Vmin und Vmax werden an Potentiometern eingestellt.

Volumenstromregelung

  • Volumenstromregler arbeitet kanaldruckunabhängig
  • Druckschwankungen bewirken keine bleibenden Volumenstromabweichungen
  • Eine Totzone (Hysterese), innerhalb der die Stellklappe nicht bewegt wird, sorgt für stabile Regelung
  • Volumenstrom-Parameter lassen sich kundenseitig verändern

Easy controller LMV-D3AL-F

Supply voltage (AC)

24 V AC ± 20 %, 50/60 Hz

Supply voltage (DC)

24 V DC −10/+20 %

Power rating (AC)

3.5 VA max.

Power rating (DC)

2 W max.

Running time for 90°

120 – 150 s

Setpoint value signal input

0 – 10 V DC, Ra > 100 kΩ

Actual value signal output

0 – 10 V DC, 0.5 mA max.

IEC protection class

III (protective extra-low voltage)

Protection level

IP 20

EC conformity

EMC to 2014/30/EU, low voltage to 2014/35/EU


Easy controller 227V-024T-05-013

Supply voltage (AC)

24 V AC ± 20 %, 50/60 Hz

Supply voltage (DC)

24 V DC ± 20 %

Power rating (AC)

5 VA max.

Power rating (DC)

3 W max.

Running time for 90°

100 s

Setpoint value signal input

0 – 10 V DC, Ra > 100 kΩ

Actual value signal output

0 – 10 V DC, 0.5 mA max.

IEC protection class

III (protective extra-low voltage)

Protection level

IP 20

EC conformity

EMC according to 2014/30/EU


Easy controllers LMV-D3A and LMV-D3A-F

Supply voltage (AC)

24 V AC ± 20 %, 50/60 Hz

Supply voltage (DC)

24 V DC −10/+20 %

Power rating (AC)

5 VA max.

Power rating (DC)

2.5 W max.

Running time for 90°

110 – 150 s

Setpoint value signal input

0 – 10 V DC, Ra > 100 kΩ

Actual value signal output

0 – 10 V DC, 0.5 mA max.

IEC protection class

III (protective extra-low voltage)

Protection level

IP 20

EC conformity

EMC according to 2014/30/EU


Easy controller 227V-024T-05-002

Supply voltage (AC)

24 V AC ± 20 %, 50/60 Hz

Supply voltage (DC)

24 V DC ± 20 %

Power rating (AC)

5 VA max.

Power rating (DC)

3 W max.

Running time for 90°

100 s

Setpoint value signal input

0 – 10 V DC, Ra > 100 kΩ

Actual value signal output

0 – 10 V DC, 0.5 mA max.

IEC protection class

III (protective extra-low voltage)

Protection level

IP 20

EC conformity

EMC according to 2014/30/EU


Easyregler 227V-024T-15-002

Versorgungsspannung (Wechselspannung)

24 V AC ± 20 %, 50/60 Hz

Versorgungsspannung (Gleichspannung)

24 V DC ± 20 %

Anschlussleistung (Wechselspannung)

Max. 5 VA

Anschlussleistung (Gleichspannung)

Max. 3 W

Laufzeit für 90°

150 – 270 s

Eingang Sollwertsignal

0 – 10 V DC, Ra > 100 kΩ

Ausgang Istwertsignal

0 – 10 V DC, max. 0,5 mA

Schutzklasse

III (Schutzkleinspannung)

Schutzgrad

IP 20

EG-Konformität

EMV nach 2014/30/EU


Easy controller SMV-D3A

Supply voltage (AC)

24 V AC ± 20 %, 50/60 Hz

Supply voltage (DC)

24 V DC −10/+20 %

Power rating (AC)

6 VA max.

Power rating (DC)

3 W max.

Running time for 90°

110 – 150 s

Setpoint value signal input

0 – 10 V DC, Ra > 100 kΩ

Actual value signal output

0 – 10 V DC, 0.5 mA max.

IEC protection class

III (protective extra-low voltage)

Protection level

IP 20

EC conformity

EMC according to 2014/30/EU


Variants, Product details

  • Variants
  • Product details

Easyregler für VVS-Regelgeräte

Artikelnummer Typ VVS-Regelgeräte, Serie

M466EU1

LMV-D3AL-F

LVC

M466EU2

227V-024T-05-013

LVC

M466ES1

LMV-D3A-F

TVR

M466DC3

227V-024T-05-002

TVR

A00000053055

227V-024T-15-002

TVJ, TVT

M466ES3

SMV-D3A

TVT

M466ES2

LMV-D3A

TZ-Silenzio, TA-Silenzio, TVZ, TVA


Das Easy-Prinzip

Electrical connection, Commissioning, Characteristics

  • Commissioning

Inbetriebnahme

  • Potentiometer entsprechend den minimalen und maximalen Volumenströmen kundenseitig einstellen
  • Einstellwerte von der Volumenstromskala (auf jedem VVS-Regelgerät) ablesen
  • Volumenstromregelbereich beachten, insbesondere zulässige Werte für den minimalen Volumenstrom nicht unterschreiten
  • Volumenstromregelbereich LVC, TVR, TZ-Silenzio, TA-Silenzio, TVZ, TVA: 10 – 100 %
  • Volumenstromregelbereich TVJ, TVT: 20 – 100 %
  • Nach Einbau, Verdrahtung und Volumenstromeinstellung ist das VVS-Regelgerät betriebsbereit
  • Transparente Schutzhaube des Easyreglers nur kurzzeitig während der Verdrahtung und Inbetriebnahme abnehmen

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.


Contact

We are here for you

Visual contact Visual contact

Please specify your message and type of request.
Tel.: +91 (0) 22 6775-1600 | Fax: +91 (0) 226775-1613

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Visual contact Visual contact

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +91 (0) 22 6775-1600 | Fax: +91 (0) 226775-1613

Contact

We are here for you

Visual contact Visual contact

Please specify your message and type of request.
Tel.: +91 (0) 22 6775-1600 | Fax: +91 (0) 226775-1613

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Visual contact Visual contact

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +91 (0) 22 6775-1600 | Fax: +91 (0) 226775-1613